IK Rating
IK ratings are defined as IKXX, where “XX” is a number from 00 to 10 indicating the degrees
of protection provided by electrical enclosures (including luminaires) against external
mechanical impacts. The IK rating scale identifies the ability of an enclosure to resist
impact energy levels measured in joules (J). IEC 62262 specifies how the enclosure must
be mounted for testing, the atmospheric conditions required, the quantity and distribution
of the test impacts and the impact hammer to be used for each level of IK rating
IK00 Not protected
IK01 Protected against 0.14 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 56 mm above impacted surface.
IK02 Protected against 0.2 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 80 mm above impacted surface.
IK03 Protected against 0.35 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 140 mm above impacted surface.
IK04 Protected against 0.5 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 200 mm above impacted surface.
IK05 Protected against 0.7 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 280 mm above impacted surface.
IK06 Protected against 1 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 400 mm above impacted surface.
IK07 Protected against 2 joules impact.
Equivalent to impact of 0.5 kg mass dropped from 400 mm above impacted surface.
IK08 Protected against 5 joules impact.
Equivalent to impact of 1.7 kg mass dropped from 300 mm above impacted surface.
IK09 Protected against 10 joules impact.
Equivalent to impact of 5 kg mass dropped from 200 mm above impacted surface.
IK10 Protected against 20 joules impact.
Equivalent to impact of 5 kg mass dropped from 400 mm above impacted surface.